Design & Materials
Comparing terminal-block current ratings: put the test conditions beside the amperes
Summary: An electrical engineer comparing two terminal blocks needs to know whether their current figures describe the same job. Start a comparison row for the complete connection, including its conductor and loading arrangement. A larger headline number is useful only when its conditions fit the intended installation.
Read the thermal evidence
Würth Elektronik’s ANE006d (22 May 2026) is specifically about its terminal blocks. It explains that rated current can differ with the test standard and permitted temperature rise. Its example uses three poles in series, 12 AWG wire and an enclosure that limits airflow. The middle clamp is hotter than the outer clamps. The same note limits square-law temperature-rise estimates to the same connector and environmental conditions; it also shows resistance and temperature rise changing as ambient temperature increases. These are manufacturer measurements, not results obtained by MTTJ.
That leaves a practical distinction: a calculation can help plan a comparison, while the applicable product curve and representative test evidence decide whether a proposed operating point is supported. Do not transfer this note’s curves to another manufacturer’s connector.
Build a comparison that can survive a supplier change
Use this working table before accepting a current figure into the design review. It is an editorial worksheet, not a certification test procedure.
Scroll tables horizontally to read every column.
| Comparison field | Record for each option | If it is missing |
|---|---|---|
| Exact connection | Terminal-block and mating-part identifiers, document revision, conductor size and termination specification | Request the applicable drawing and current data sheet |
| Loading | Which poles carry current simultaneously and the continuous or intermittent load pattern | Mark the rating comparison incomplete |
| Thermal setting | Local ambient condition, enclosure and airflow represented by the evidence | Ask which evidence represents the intended installation |
| Rating basis | Named test method, temperature-rise limit, measurement location and applicable curve | Keep the number as an unqualified catalog entry |
| Acceptance | Approved component limits, application requirement and responsible engineering sign-off | Leave the operating current undecided |
Keep the source document beside every filled row. A blank is preferable to borrowing a value from a similar housing.
A worked comparison without inventing a safe current
Suppose option A has a higher catalog current but the supplier has not stated the conductor or pole loading. Option B has a lower number with those conditions documented. The table does not declare B electrically superior. It makes the next action specific: request A’s missing conditions, and check whether B’s documented arrangement matches the installation. Neither number alone settles the decision.
If both suppliers provide applicable curves but the proposed enclosure differs from the documented setup, record that difference as a test question. Have the responsible engineer specify the representative assembly, instrumentation, stabilization criterion and stop limits before energizing a sample. Retain the actual configuration with the result so a later conductor or loading change can be assessed against it.
The useful output of this review is one of two things: an operating point supported by applicable evidence and engineering acceptance, or a precise request for the evidence still missing. This worksheet deliberately supplies no universal current, temperature-rise allowance or compliance conclusion.
Source: Würth Elektronik, ANE006d, Derating of Connectors, sections 1-3, read 16 November 2026. The source’s product scope remains in force. Revisit the comparison when the part, conductor, loading, thermal environment or source revision changes.
AI-assisted technical writing.